ADAM-6000 Series User Manual

228

Function Code 08
Echoes received query message. Message can be any length up to half the
length of the data buffer minus 8 bytes.

Request message format for function code 08:

Example: 01 08 00 02 00 04
Response message format for function code 08:

Example: 01 08 00 02 00 04

Function Code 15 (0F hex)
Forces each coil in a sequence of coils to either ON or OFF.
Request message format for function code 15:

Example: Request to force a series of 10 coils starting at address 00017
(11 hex) in ADAM-6000 module.
01 0F 00 11 00 0A 02 CD 01
The query data contents are two bytes: CD 01 hex, equal to 1100
1101 0000 0001 binary. The binary bits are mapped to the addresses in
the following way.
Bit: 1 1 0 0 1 1 0 1 0 0 0 0 0 0 0 1

Address (000XX): 24 23 22 21 20 19 18 17

- - - - - - 26 25

Command Body

Station

Address

Function

Code

Any data, length limited to approximately half the length of the

data buffer

Command Body

Station

Address

Function

Code

Data bytes received

Command Body

Station

Address

Function

Code

Start

Address

High Byte

Start

Address

Low Byte

Requested

Number

of Coil High

Byte

Requested

Number

of Coil Low

Byte

Byte

Count

Force

Data

High

Byte

Force

Data

Low

Byte