Name

Read Analog Input from All Channels

Description Returns the input data from all analog input channels in a

specified module.

Syntax #aa(cr)

# is a delimiter character.
aa (range 00-FF) represents the 2-character hexadecimal
slave address of the ADAM-6000 module you want to
interrogate. (Always 01)
(cr) is the terminating character, carriage return (0Dh).

Response

>(data)(data)(data)(data)(data)(data)(data)(data)(data)(cr) if
the command is valid.
?aa(cr) if an invalid operation was entered.
There is no response if the module detects a syntax error or
communication error or if the address does not exist.
> delimiter indicating a valid command was received.
? delimiter indicating the command was invalid.
(cr) is the terminating character, carriage return (0Dh).

Note:

The latest data returned is the Average value of the preset
channels in this module.

Example

command: #01(cr)
response: >+10.000+10.000+10.000+10.000+10.000

+10.000+10.000+10.000+10.000