139

Chapter 6

#aaML
Name

Read Minimum Value

Description Read the minimum values from all analog input channels in

a specified module

Syntax #aaML(cr)

# is a delimiter character.
aa (range 00-FF) represents the 2-character hexadecimal
slave address of the ADAM-6000 module to be read.
(Always 01)
ML represents the read minimum value command.
(cr) is the terminating character, carriage return (0Dh)

Response

>(data)(data)(data)(data)(data)(data)(data)(data)(data)(cr)
if the command is valid.
?aa(cr) if an invalid operation was entered.
There is no response if the module detects a syntax error or
communication error or if the address does not exist.
> delimiter indicating a valid command was received.
? delimiter indicating the command was invalid.
aa (range 00-FF) represents the 2-character hexadecimal
slave address of an ADAM-6000 module.
(cr) is the terminating character, carriage return (0Dh)

Example

command: #01ML(cr)
response:>+10.000+10.000+10.000+10.000

+10.000+10.000+10.000+10.000+10.000

The command asks the specific module at address 01h to
send historic minimum value from all AI channels.

Note:

The latest data returned is the Average value of the preset

channels in this module.