Figure 8 ne830 display, Figure 9 rectifier and converter type badge, Aux display - ne830a (optional) – GE Industrial Solutions H5692448 Power Systems Infinity M1 (NE-M) User Manual

Page 12: Rectifiers and converters

Advertising
background image

NE-M

Installation Guide

H5692448

CC848815325 r06 May 2013

12

Aux Display - NE830A (Optional)

The Aux Display is a voltage monitor that alarms when the voltage of the power system is out of the normal operating

range. It is mounted on the door of the distribution box.

Figure 8 NE830 Display

• Fully independent of the main system controller

• Displays one or two system voltages and battery state:

• Single voltage systems, -48V, +24V
• Dual voltage systems, -48V and +24V with common return

• The display and LED color indicates battery charge state and wiring errors:

• Green display = batteries are not discharging
• Red display = batteries are discharging
• Amber display = wiring error

• A Battery on Discharge alarm relay with form-C contacts is provided
• Can be panel, wall or frame rail mounted within 150 ft of the power system

Rectifiers and Converters

NE-S

eries rectifiers and converters are hot-pluggable for quick, simple, plug-and-play installation without tools.

Figure 9 Rectifier and Converter Type Badge

NE Eco

Rectifiers

Input

AC or DC (PV or solar)

Compatibility All Infinity Rectifier Positions
Eco Feature

MPPT (Maximum Power Point Tracking) maximizes power harvested from PV arrays

NE Non-Eco Rectifiers

Input

AC only

Compatibility All AC powered Infinity Rectifier Positions

6

6

Non Eco rectifiers will not function properly when powered by DC (PV or solar) input in Eco systems.

Type Badge