Installation

Follow all site engineering instructions. This section is provided only as a guide.

Preparation

Safety

Read and follow all safety statements, warnings, and precautions in the Safety section of this manual and manuals of

all other equipment before installing, maintaining or repairing the equipment.

Installation Tools

You will need the following tools.

• Wire cutters and strippers
• Heat shrink gun
• 5/16-inch (8 mm) hex driver
• Digital meter with an accuracy of ±0.02%
• Screw drivers (flat-blade and Phillips)
• ESD wrist strap
• 24 or 48V test load
• Calibrated clamp-on dc current meter (0.1 ADC

sensitivity)

• Torque wrench
• Socket wrenches:

• 7/16” and 9/16” - cable connections
• 19 mm - anchor bolts

• 12" extension for socket
• Masonry drill kit as required
• Compression for installation of various

compression lugs

• Protective canvas
• Insulating rubber mat
• Standard insulated installation tools, screwdrivers,

etc.

• Controller Manual

Galaxy Pulsar Plus Family Product Manual

or

Galaxy Millennium II Installation and User’s Guide

• Windows-based personal computer laptop (PC)

and cable to connect the PC communications port

to the local port of the controller or a CAT5 LAN

cable. (Optional. See the controller manual for

more information).

Equipment Identification

Identify the equipment you have received. Follow procedural steps which match the equipment being installed.

Anchor Frame

Ventilation space is required to the rear of the equipment: 4” to solid surface, 6” to heat producing surface.

Floor Mounted Frame

Using the 847135688 Floor Anchor Kit (recommended):

Anchor Type (Hilti)

Wrench

Torque

(4) 12 mm Cap Bolts

19 mm

720 in-lb
60 ft-lb
82 Nm


Note: For systems with tray mounted batteries at sites requiring Seismic Zone 4 rating, (2) 847135688 kits are required

to provide (8) floor anchors.

Note: If using Equivalent Floor Anchors, make sure the floor anchors are rated for this application.