NE-M
Installation Guide
H5692448
CC848815325 r06 May 2013
55
Step
Action
3
Apply appropriate terminals (if necessary) to the cable after removing the supplied had 1/4 inch Faston ®
terminals:
Table 8 Power Connections - NE830
Pin #
Wire Color
Signal Name
Connect to:
1
(Green)
Earth Ground Frame Ground
2
(White)
24V+/-
24V point to be monitored (+24V or -24V)
3
(Red)
48V-
-48V point to be monitored (-48V only)
4
(Black)
Common
Return
Return for signals on pins 2 & 3
4
Connect and wire connection to NE830A. Alarm cable comcodes are
15ft: CC847922101, 150 ft: CC848804765.
Figure 77 NE830 Alarm Cable Connector
Table 9 Alarm Connections - NE830
Pin #
Wire Color
Signal Name
1 Black
Common
2 Brown
Open on Alarm
3 Bare
Close on Alarm
Alarm Cable
Connector