NE-M

Installation Guide

H5692448

CC848815325 r06 May 2013

41

Step

Action – Pulsar Plus

3

Configure alarm relays to “Open On Alarm” or “Close On Alarm” as specified in site engineering instructions.

Each Alarm Relay Jumper select “Open On Alarm” or “Closed On Alarm” for one alarm signal and each signal

output can be configured independently.

Carefully move each Alarm Relay Jumper to select “Open On Alarm” or “Close On Alarm” position as per site

engineering instructions with an insulated tool.

Figure 61 Alarm Relay Jumper Positions - Pulsar Plus

The following table contains the alarms along with the factory default alarm assignments to user relays R1-

R7.

Utilize the web interface to change any of the alarm user relay alarm assignments.

Table 3 Alarm Defaults – Standard Pulsar Plus

Jumper

Number

Signal

Name

Standard

Defaults

1

PCR

Power Critical Alarm severity indicator

2

PMJ

Power Major Alarm severity indicator

3

PMN

Power Minor Alarm severity indicator

4

R1

BD - Battery on Discharge alarm

5

R2

VLV - Very Low Voltage alarm

6

R3

FAJ - External Fuse Major alarm

7

R4

ACF – single rectifier input (AC or DC) Fail alarm

8

R5

RFA - single Rectifier Fail alarm

9

R6

MRFA - multiple Rectifier Fail alarm

10

R7

HV - High Voltage shutdown alarm

4

Using optional ES771 Mid-String Voltage Modules?

Yes – go to Step 4.

No – Go to Step 5.