Battery or battery stand mounted frame, Sub-frame mounted systems, Figure 15 battery stand mount – GE Industrial Solutions H5692448 Power Systems Infinity M1 (NE-M) User Manual

Page 18

Advertising
background image

NE-M

Installation Guide

H5692448

CC848815325 r06 May 2013

18

Battery or Battery Stand Mounted Frame

Step

Action

1

Verify that battery or battery stand is positioned to provide adequate ventilation space to the rear of the

equipment: 4” to solid surface, 6” to heat producing surface (shown in the floor mounted frame figure below)
Place and secure frame to battery or battery stand per instructions provided with the battery stand or

adapter.

Figure 15 Battery Stand Mount

Sub-frame Mounted Systems:

Sub-frame mounted systems can be mounted in any standard 23” equipment mounting rack or frame with EIA-310

standard 1-3/4” rack spaces or 1” standard rack spaces. The brackets are 36.75” (21U) tall. Comcode CC848819607 kit

provides two brackets and 20 12-24 mounting screws.

Minimum Distance to Surface
7.5" to Solid Surface

9.5" to Heat Producing Surface