Battery or Battery Stand Mounted Frame
Step
Action
1
Verify that battery or battery stand is positioned to provide adequate ventilation space to the rear of the
equipment: 4” to solid surface, 6” to heat producing surface (shown in the floor mounted frame figure below)
Place and secure frame to battery or battery stand per instructions provided with the battery stand or
adapter.
Figure 15 Battery Stand Mount
Sub-frame Mounted Systems:
Sub-frame mounted systems can be mounted in any standard 23” equipment mounting rack or frame with EIA-310
standard 1-3/4” rack spaces or 1” standard rack spaces. The brackets are 36.75” (21U) tall. Comcode CC848819607 kit
provides two brackets and 20 12-24 mounting screws.
Minimum Distance to Surface
7.5" to Solid Surface
9.5" to Heat Producing Surface