Install bsm6 modem, Install optional controller peripherals, Install rectifiers/converters – GE Industrial Solutions H5692448 Power Systems Infinity M1 (NE-M) User Manual

Page 50: Figure 69 lan connection - millennium ii, Figure 70 insert rectifier

Advertising
background image

NE-M

Installation Guide

H5692448

CC848815325 r06 May 2013

50

Step

Action – Millennium II

6

Local RS232 Serial Port Connector


Connect notebook computer, PC or external modem to

RS232 port.
The Local Port connector is at the lower left of the

controller card. This connector is factory cabled to the

Local Port connector on front right of the front panel, for

convenient local connection of a laptop PC.
If connecting to a modem or other device which is

connected permanently, use the Local Port connector on

the controller card.
Connect to the RS-232 connector as Data Circuit-

terminating Equipment (DCE).

Figure 69 LAN Connection - Millennium II

Install BSM6 Modem

The optional BSM6 Modem is field installed. Instructions accompany the modem.

Install Optional Controller Peripherals

Optional Controller Peripherals are field installed. See the controller manual and instructions accompany the

options.

Install Rectifiers/Converters

Rectifier/Converter Installation Procedure

Step

Action

CAUTION: Improper Operation

Install only Eco rectifiers in Eco system DC (PV or solar) powered positions.

20

Eco systems require Eco rectifiers in all DC powered positions.

Eco rectifiers have unique badge symbols - Table 1.

CAUTION

:

Equipment Damage

Do not install rectifiers before battery bus voltage and polarity has been verified.

Rectifiers and system damage will result from incorrect battery bus polarity.

The damage may not be immediately evident.

1

Is this a DC (PV or solar) powered rectifier position in an Eco system?

Yes – Proceed

No – go to Step 2.

2

Verify rectifier is Eco type by examining the rectifier type badge - Table 1

3

Verify rectifier Output Voltage by examining the rectifier type badge - Table 1

4

Slide the rectifier/converter part way into a slot.

Figure 70 Insert Rectifier

20

Non-Eco rectifiers may be installed in AC powered position – NOT RECOMMENDED.

Advertising