Pulsar Controller Status

Display

Millennium Controller

Status Display

Rect/

Conv

LEDs

Dist.

Module

LED

Possible Problem(s)

Possible Solution(s)

No Alarm, but

individual Shunt

Currents are

displayed at or

above their

maximum display

values (≥600A for

loads, ≥800A for

battery)

Norm

green

green

One or both of the QS871A

shunt inputs is open-circuit.

1. Verify that the respective shunt has its green and yellow wire

connections attached used for the current measurements.

2. Verify the shunt connection to the QS871A is good by

verifying the green and yellow wire connections from the

shunt follows through to the 10-pin connector at the

respective QS871A.

Display green

green green green

BD AC DC

Normal

green