Installation Guide

H5692448

CC848815325 r06 May 2013

59

Step

Configuration Attribute

to Change

Menu Path/Action = Millennium II

Format

This field allows you to select one of the following date formats: MM/DD/YY,

DD/MM/YY, YY/MM/DD, MM/DD/YYYY, DD/MM/YYYY, YYYY/MM/DD. Use the <+> or

<-> key to select the desired format and press <ENTER> to save the change.

Month

Use this field to change the month; the possible value is from 1 to 12.

Day

Use this field to change the day of the month; the possible value is from 1 to 31.

Year

Use this field to change the year; the possible value is from 1992 and up.

NOTE Please note that the system will validate the entries before the system date is modified.

2

TIME
Format

This field allows you to select one of the following time display formats: 12 or 24

hour. Use the <+> or <-> key to select the desired format and press <ENTER> to

save the change.

Time

Allows you to change/set the time.

Daylight

Enables or Disables Daylight Savings per the new standards created by the

Energy Policy Act of 2005. (Started in 2007.)

3

Batteries

Model

The configuration of this field selects the installed battery type from a list of pre-

defined battery types used in reserve time prediction and enhanced battery test

features. Move the cursor to the field and use the <+> or <-> key to adjust the

threshold value. Press <ENTER> to save the change.

Strings

The configuration of this field selects the number of battery strings in the system.

This parameter is used in reserve time prediction and enhanced battery test

features. Move the cursor to the field and use the <+> or <-> key to adjust the

threshold value. Press <ENTER> to save the change.

Cells/String

The configuration of this field selects the number of installed cells in the battery

strings. This parameter is used in reserve time prediction and enhanced battery

test features. Move the cursor to the field and use the <+> or <-> key to adjust

the threshold value. Press <ENTER> to save the change.

Type

The configuration of this field selects the battery type, Flooded or Valve

Regulated (sealed). This parameter is used in reserve time prediction and

enhanced battery test features. Move the cursor to the field and use the <+> or

<-> key to adjust the threshold value. Press <ENTER> to save the change.