Battery or Battery Stand Mounted Frame

If required by local code or practice, battery or battery stand mounted frames may be grounded to the frame or chassis

of the other equipment. Select a Frame Ground landing at the side of the frame and clean.

Step

Action

1

Secure Frame Ground connection with provided

hardware:

(2) ¼-20 x ¾” HH Bolt
(2) ¼-inch lock washer
(2) ¼-inch flat washer

If required by local code or practice, treat with an

oxidation inhibitor such as NO-OX.

Torque to 65 in-lb - 7/16” socket.

Note: Lug landings are 1/4” on 5/8” centers.

Figure 18 Ground Short Frame

Connect Central Office Ground (COG)

Step

Action

1

Secure COG connection with provided hardware:

(2) 3/8-16 nut

(2) 3/8-inch lock washer

(2) 3/8-inch flat washer

If required by local code or practice, treat with an

oxidation inhibitor such as NO-OX.

Torque to 240 in-lb - 9/16” socket.

Figure 19 CO Ground Landing


Note: Lug landings are 3/8” on 1” centers.