NE-M

Installation Guide

H5692448

CC848815325 r06 May 2013

62

Manual Contactor Control and Alarms

28

Step

Action

1

Open the contactor by controller command (Menu > Control / Operations > Disconnects).

2

Verify the controller reports a Contactor Open alarm.

29

3

Close the contactor by controller command.

4

Verify the alarms clear and the controller returns to Normal.

28

Skip if contactors are not present.

29

Contactor Open Alarm may be delayed by imminent LVD Alarm delay if enabled and configured.