NE-M

Installation Guide

H5692448

CC848815325 r06 May 2013

33

Step

Action

24V Battery Strings


Connect the factory-wired battery return cables

to the V- posts (left most posts) of both strings.

Torque to battery manufacturer’s specification.

Figure 48 Battery Return Cable Direct +24V

Battery installation is complete.

External Battery Connection

Step

Action

Is an external Battery Shunt panel installed

16

?

Yes – go to Step1.

No – go to Step4.

1

Battery Landings are 1/4-20 studs on 5/8” centers

spaced 3/4” apart (7 landings).

Lug adaptors use 2 landing positions and provide

3/8-16 studs on 1” centers (provided).

Figure 49 External Battery Shunt Panel

Are lug adapters required?

Yes – go to Step2.

No – go to Step3.

2

Install Lug Adapters

Remove 1/4-20 nuts (4) from landing.

Place lug adapter
Secure lug adapter with 1/4-20 nuts (4).

If required by local code or practice, treat with an

oxidation inhibitor such as NO-OX.

Torque to 65 in-lb - 7/16” socket.

Figure 50 External Battery Shunt Panel Lug Adapters

16

Eco systems less than 600A use an external battery panel.

External Battery Connections

¼-20 Studs

Lug Adapter