Step

Action

2

Snap loose L1 and L2 plastic dividers on Input terminal

blocks for each single fed rectifier pair.

Figure 28 shows rectifier AC dual feed jumper positions.

Figure 30 Input Jumper Dividers

3

Install AC bridging jumpers connecting each AC fed

rectifier pair L1 positions.

Install AC bridging jumpers to connect each AC fed

rectifier pair L2 positions.

Torque to 10 in-lb.

Figure 31 AC Bridging Jumper

4

CAUTION: Equipment Damage or Malfunction

NE-M Eco

systems must keep PV input feeds separate from AC input feeds.

The PV/AC partition separates PV inputs from AC inputs.

Connect PV input feeds only to the PV section of the Input Panel.

Connect AC input feeds only to the AC section of the Input Panel

CAUTION: Equipment Damage or Malfunction

NE-M Eco

systems PV input feeds must be connected as follows:

Positive PV to L1

Negative PV to L2.

5

Pull and terminate input feed wires to the terminal blocks

in the Input Panel.

• ac input feeds to the AC section of the Input

Panel

• PV input feeds to the PV section of the Input

Panel

Positive PV to L1

Negative PV to L2.


Torque to 10 in-lb.

Figure 27 shows rectifier and shelf numbering.

Figure 32 Input Panel Sections

L2

L1

R1

R1

Snap Loose

Divider

with Pliers

R13 and R14

L1 AC feed

R13 and R14

L1 Bridging Jumper

PV/AC Partition

Eco

only

PV Section

NE-M

Eco only

ac Section

NE-M

Eco only

Advertising