Step

Action

24V Battery Strings


Connect the 2/0 cable between the V- post of the

right-most battery of the left string and the input

bus of the left disconnect switch.

Connect the 2/0 cable between the V- post of the

right-most battery of the right string and the

input bus of the right disconnect switch.

Torque to battery manufacturer’s specification.

Figure 40 Battery Cable +24V

5

Connect Battery Return Cable (ground side)

48V Battery Strings


Connect the factory-wired battery return cable to

the V+ post of the right-most battery.

Torque to battery manufacturer’s specification.

Figure 41 Battery Return Cable -48V

24V Battery Strings


Connect the factory-wired battery return cables

to the V- posts (left most posts) of both strings.

Torque to battery manufacturer’s specification.

Figure 42 Battery Return Cable +24V

Battery installation is complete.

Follow site engineering instructions regarding when to turn the disconnect switches ON.