Rectifiers/converters, Figure 80 rectifier face plate, Table 11 rectifier/converter leds – GE Industrial Solutions H5692448 Power Systems Infinity M1 (NE-M) User Manual

Page 70: Rectifier/converter troubleshooting, Rectifier/converter leds

Advertising
background image

NE-M

with Pulsar or Millennium II Installation Guide

H5692448

CC848815325 r06 May 2013

70

Rectifiers/Converters

Status of a rectifiers and converters is provided by LEDs on their faces, and by extensive real time data, alarm and

event history accessible through the system controller.

Figure 80 Rectifier Face Plate

Non-Eco rectifiers powered by PV (solar) panels will not operate properly.

• Under some conditions their LEDs may indicate normally operation: Norm LED ON.
• Various other LED conditions and rectifier status (observed via the controller) may occur with variations in

DC input and load.

Rectifier/Converter Troubleshooting

1. Verify rectifier positions per the procedure in the Verify Rectifier Positions section.
2. Observe and compare Rectifier/Converter Status LEDs with Controller Status information.
3. Use the table below as a troubleshooting guide.

Rectifier/Converter LEDs

Table 11 Rectifier/Converter LEDs

LEDs

Condition

Normal operation: No alarms, inputs and outputs are in their normal range, communicating

with the system controller.

Unpowered: No input or output voltage present.
1. Remove and reinsert unit.
2. Check input voltage with a voltmeter;

if input voltage is present, replace unit.

3. Check output bus voltage with a voltmeter;

if output bus voltage is present, replace unit.

Standby: The unit is okay, but has been placed in Standby by the controller and is not

delivering power.

Note: If a unit in standby loses communications with the controller it will exit Standby mode

and deliver power

Type Badge

Cooling Fan

Air Inlet

Serial Number and CLEI Code

(text and barcode)