GE Industrial Solutions H5692448 Power Systems Infinity M1 (NE-M) User Manual

Page 65

Advertising
background image

NE-M

with Pulsar or Millennium II Installation Guide

H5692448

CC848815325 r06 May 2013

65

Pulsar Controller Status

Display

Millennium Controller

Status Display

Rect/

Conv

LEDs

Dist.

Module

LED

Possible Problem(s)

Possible Solution(s)

MAJ Multiple Rectifier

Fail,
MAJ Battery on

Discharge

Fail

red

(multiple

Rect)

green

Multiple rectifier outputs have

dropped below 18V (36V); rectifiers

have shut down

31

.

1. Reset the rectifiers by removing the rectifiers, waiting

approximately 30 seconds, and replacing the rectifiers.

2. If problem not corrected, replace rectifiers.

• Excessive ambient temperature;

multiple rectifiers have shut

down

31

.

• Multiple rectifiers have failed.

1. Verify that there is no obstruction of the vertical airflow path

and fans are turning.

2. Reset rectifies by removing them, waiting approximately 30

seconds, and replacing them.

3. If problem persists, replace the rectifiers.
4. If problem still persists, call your local field representative.

Fail

red

(all Rect)

green

• All rectifier outputs have dropped

below 18V (36V); all rectifiers

have shut down

31

.

• Defective controller.

1. Remove controller and reset the rectifiers by removing the

rectifiers, waiting approximately 30 seconds, and replacing

the rectifiers.

2. If output voltage does not go to set-point previously set by

user, call your local field representative.

MAJ High Voltage

Fail

red

(multiple

Rect)

green

• High output voltage from

rectifier(s).

• Rectifier(s) high voltage shut

down

31

.

• Internal rectifier(s) failure.
• VHV threshold set below float set

point.

1. Check and adjust VLV threshold to above float set point.
2. Reset the rectifier(s) by removing the rectifier(s), waiting

approximately 30 seconds, and replacing the rectifier(s).

3. If problem persists, replace rectifier(s).
4. If problem still persists, call your local field representative.

31

When a power unit senses an over- or under-voltage condition it will shutdown, wait 10 seconds, and then attempt to restart. If the over- or under-voltage condition

remains it will cycle again. If the over- or under-voltage condition remains after 3 restart attempts the power unit will lock out, and user intervention is required to restart.

BD AC DC

red green green

-54.48

V1

1000A

FLOAT

Display Red

Minor

Rectifier/

red

Converter

amber

green green green

BD AC DC

-54.48

V1

1000A

FLOAT

Display Red

Minor

Rectifier

red

amber