GE Industrial Solutions H5692448 Power Systems Infinity M1 (NE-M) User Manual

Page 66

Advertising
background image

NE-M

with Pulsar or Millennium II Installation Guide

H5692448

CC848815325 r06 May 2013

66

Pulsar Controller Status

Display

Millennium Controller

Status Display

Rect/

Conv

LEDs

Dist.

Module

LED

Possible Problem(s)

Possible Solution(s)

MAJ Fuse Major

Norm

green

red

One or more output circuit

breakers or fuses have opened.

1. Clear circuit fault(s).
2. Reset circuit breaker(s) or replace fuse(s).

MAJ Contactor Open

Norm

green

Red

One or more LVD contactors are

manually forced open.

Place disconnect switch(s) in ON position.

MIN Battery High

Temperature

Norm

green

green

Batteries have exceeded

temperature threshold set by user.

1. Check the threshold setting.
2. Call your local field representative.

BD AC DC

-54.48

V1

1000A

FLOAT

Display Red

green green red

Minor

Distribution

red

amber

BD AC DC

-54.48

V1

1000A

FLOAT

Display Red

green green red

Minor

Battery

red

amber

green green green

BD AC DC

-54.48

V1

1000A

FLOAT

Display Amber

Minor

Battery

amber

amber