Verify rectifier positions, Figure 75 inventory screen – GE Industrial Solutions H5692448 Power Systems Infinity M1 (NE-M) User Manual

Page 53

Advertising
background image

NE-M

Installation Guide

H5692448

CC848815325 r06 May 2013

53

Verify Rectifier Positions

Refer to site engineering instructions for rectifier type per position.

Step

Action

1

Verify that proper rectifiers are installed in all powered rectifier positions.

2

Verify that rectifiers in all DC powered positions have Eco type badges

23

- Table 1.

3

Verify that rectifiers in all DC powered positions are displayed with the Eco leaf in the ECO Support column on

the controller web Inventory report screen – Figure 75.

4

Verify that rectifiers in all DC powered positions are displayed with the “Eco leaf” in the controller web main

screen

24

Figure 76.

Figure 75 Inventory Screen

23

RECOMMENDED – Eco rectifiers in all Eco system rectifier positions (AC and DC powered).

NOT RECOMMENDED – Non-Eco rectifiers may be installed in AC powered positions of Eco systems.

Use of non-Eco rectifiers in Eco systems increases the risk of improperly filling system rectifier positions.

24

The “Eco leaf” displays for rectifier positions after being DC powered while connected to the controller.

All populated rectifier positions are reported as AC powered until DC input is applied.

Eco type rectifiers display the Eco leaf

Advertising