GE Industrial Solutions H5692448 Power Systems Infinity M1 (NE-M) User Manual

Page 64

Advertising
background image

NE-M

with Pulsar or Millennium II Installation Guide

H5692448

CC848815325 r06 May 2013

64

Pulsar Controller Status

Display

Millennium Controller

Status Display

Rect/

Conv

LEDs

Dist.

Module

LED

Possible Problem(s)

Possible Solution(s)

MAJ Battery on

Discharge

Norm

green

green

System voltage has fallen below

the battery on discharge threshold

set by the user.

1. Investigate other alarms that may be present such as rectifier

related problems.

2. If AC power is present but the system voltage remains low,

call your local field representative.

Norm

amber

green

Rectifier is in current limit.

MAJ Battery on

Discharge and AC Fail

INF

amber

green

• Rectifier not receiving ac power.
• ac input voltage is out of range.

MIN Rectifier Fail

Fail

red

(one

Rect)

green

• Rectifier output has dropped

below 18V (36V), rectifier has

shut down

30

.

• Excessive ambient temperature,

rectifier has shut down.

• A rectifier or rectifier fan has

failed.

• A rectifier high voltage shut

down

30

.

1. Verify that there is no obstruction of the airflow path and fans

are turning.

2. Reset the rectifier by removing the rectifier, waiting

approximately 30 seconds, and replacing the rectifier.

3. If problem persists, replace the rectifier.
4. If problem still persists, call your local field representative.

30

When a rectifier or converter senses an over- or under-voltage condition it will shutdown, wait 4 seconds, and then attempt to restart. If the over- or under-voltage condition

remains it will cycle again. If the over- or under-voltage condition remains after 3 restart attempts the unit will lock out, and user intervention is required to restart.

BD AC DC

red green green

-54.48

V1

1000A

FLOAT

Display Red

Major

Battery on

red

Discharge

red

Major

Battery on

red

Discharge

red

BD AC DC

red amber green

Display Red

-54.48

V1

1000A

FLOAT

Major

AC Battery on

red

Sys Discharge

amber

red

green green green

BD AC DC

-54.48

V1

1000A

FLOAT

Display Amber

Minor

Rectifier/

amber

Converter

amber

The image part with relationship ID rId198 was not found in the file.