NE-M

Installation Guide

H5692448

CC848815325 r06 May 2013

42

Step

Action – Pulsar Plus

5

Configure the 1-Wire serial bus reference

The ES771 modules must be referenced to the most negative potential of the DC bus. This reference is

achieved by the proper setting of Jumper 11 next to the relay configuration jumpers. Following are the

appropriate settings for negative and positive power plants. The jumper is set in the factory for positive

systems unless the controller is shipped with an assembled system that has a pre-determined primary output

bus. It is suggested that an insulated tool be used to set the jumpers.

Figure 62 1-Wire Jumper - Pulsar Plus

Connect Controller Wiring – Pulsar Plus

All connections to the controller are made through appropriate cable assemblies. The controller has been designed

to separate outputs, inputs, communication, and plant specific items onto to individual connectors.

Figure 63 Controller Connections

Many systems are shipped with the appropriate controller connections wired by the factory. The following provides

a brief description of how and what to connect to the controller. Use only those sections that apply to the system

configuration.

+24V systems Jumper Position

-48V systems Jumper Position

J5

J4

J3 J2 J1