Pulsar Controller Status

Display

Millennium Controller

Status Display

Rect/

Conv

LEDs

Dist.

Module

LED

Possible Problem(s)

Possible Solution(s)

MIN Thermal Probe

Fail

Norm

green

green

Battery thermal probe failed.

1. Ensure thermal probe is properly connected to thermal probe

cable.

2. Ensure cable is properly connected to the rear of the

Distribution Module.

3. If problem persists, replace thermal probe.
4. If problem still persists, call your local field representative.

No response

Fail

red

blink

red

blink

Controller failure, all devices on the

communication bus reporting loss

of communication with controller.

1. Check controller to ensure it is properly inserted into its slot. If

so, perform the following steps:

2. Remove the controller input power connector for 1 minute

and then reset.

3. If problem persists, replace controller with new controller

board.

4. If problem still persists, call your local field representative.

MIN Minor

Communication Fail

Fail

red

blink

(one

rect)

green

Rectifier lost communication with

controller.

1. Reset the rectifier by removing the rectifier, waiting

approximately 30 seconds, and replacing.

2. If problem persists, replace the rectifier.
3. If problem still persists, call your local field representative.

Norm

green

green

Rectifier removed from a running

system, but not uninstalled.

Issue the Menu > Control / Operations > Uninstall Equipment

command for any rectifier that was removed.

green green green

BD AC DC

-54.48

V1

1000A

FLOAT

Display Amber

Minor

Battery

amber

amber

Display blank

off off off

BD AC DC

Display blank

green green green

BD AC DC

-54.48

V1

1000A

FLOAT

Display Amber

Minor

amber