Troubleshooting, System, Normal operation – GE Industrial Solutions H5692448 Power Systems Infinity M1 (NE-M) User Manual

Page 63

Advertising
background image

NE-M

with Pulsar or Millennium II Installation Guide

H5692448

CC848815325 r06 May 2013

63

Troubleshooting

System

Pulsar Controller Status

Display

Millennium Controller

Status Display

Rect/

Conv

LEDs

Dist.

Module

LED

Possible Problem(s)

Possible Solution(s)

No Alarms

Norm

green

green

Normal Operation

MIN AC Fail

INF amber

(one

Rect)

green

• Single rectifier not receiving AC

power.

• ac input circuit breaker has

opened.

• ac input voltage is out of range.

1. Verify rectifier input circuit breaker is closed.
2. Verify AC power to rectifier is available and in range.
3. If problem not corrected, replace rectifier.

Norm

green

green

A rectifier has been removed from

the system while it is unpowered.

Issue the Menu > Control / Operations > Uninstall Equipment

command for any rectifier that was removed while unpowered.

MAJ Multiple AC Fail

INF

amber

(Multiple

Rect)

green

• Multiple rectifiers not receiving

AC power.

• ac input circuit breakers have

opened.

• ac input voltage is out of range.

1. Verify rectifier input circuit breakers are closed.
2. Verify AC power to rectifiers is available and in range.
3. If problem not corrected, replace rectifiers.

Norm

green

green

One or more rectifiers have been

removed from the system while it

is unpowered.

Issue the Menu > Control / Operations > Uninstall Equipment

command for any rectifier that was removed while unpowered.

Display green

green green green

BD AC DC

Normal

green

`green amber green

-54.48

V1

1000A

FLOAT

Display Amber

BD AC DC

Minor

AC System

amber

amber

-54.48

V1

1000A

FLOAT

BD AC DC

green red green

Display Red

Minor

AC System

red

amber

Advertising