Configure Controller – Minimum

This section covers the basic operations that must be performed so that the controller is minimally configured. See

the controller manual for further detail.

Configure Pulsar Controller

Figure 78 Front Panel - Pulsar Plus Controller

This display shows the front panel display for a system with both rectifiers and converters. The display (V1 versus

V2) correlates with test jacks. The large font indicates the “Primary” or rectifier dc bus; the smaller font shows the

“Secondary” or converter dc bus.
Menu Navigation Buttons

Parameter Change

Increase or decrease the value of the selected parameter.

Navigate

Navigate menus – move to different selected menu item.

Enter Button

Enter a sub-menu or confirms a parameter change.
Go to the Main Menu from the Normal display.

ESC Button

Go up one menu level or exits a parameter change without saving.

Step

Configuration Attribute

to Change

Menu Path/Action - Pulsar

1

Date

Format

This field allows you to select one of the following date formats: MM/DD/YY,

DD/MM/YY, YY/MM/DD, MM/DD/YYYY, DD/MM/YYYY, YYYY/MM/DD. Use the <+>

or <-> key to select the desired format and press <ENTER> to save the change.

Month

Use this field to change the month; the possible value is from 1 to 12.

Day

Use this field to change the day of the month; the possible value is from 1 to

31.

Year

Use this field to change the year; the possible value is from 1992 and up.

Note: The system will validate the entries before the system date is modified.

2

Time

Plant Voltage and

Load Current

Voltage Test Jacks

RS-232 Port

Plant Status LEDs

Plant Mode

Menu Navigation

Configuration

Shunt Monitors

System

Settings

Date

Time