Pulsar Controller Status

Display

Millennium Controller

Status Display

Rect/

Conv

LEDs

Dist.

Module

LED

Possible Problem(s)

Possible Solution(s)

MAJ Major

Communication Fail

Norm

green

red

blink

• LVD Board lost communication

with the controller.

• Multiple devices no longer

communicating with the

controller.

1. Clear blinking red LEDs on all devices.

See other conditions with blinking red LEDs.

2. Correct communication with each device.

3. Issue the Menu > Control / Operations > Uninstall

Equipment command.

(This only removes this alarm for unconnected devices.)

4. Replace Distribution Module Board.
5. If problem persists, call your local field representative.

MIN Clock Battery

Low

Norm

green

green

Internal Lithium Battery Is Low.

1. The battery is not field replaceable. The controller unit must

be replaced.

2. Off-load all desired information such as alarm history,

statistics, and any field configuration that is different than the

standard.

3. Replace controller, and upload any non-standard

configuration.

green green green

BD AC DC

-54.48

V1

1000A

FLOAT

Display Red

Major

Red

green green green

BD AC DC

-54.48

V1

1000A

FLOAT

Display Amber

Minor

Controller

amber

amber