Miscellaneous Alarms

(Batteries must be connected)

Distribution Alarms

Step

Action

1

Manually connect a piece of wire from the circuit breaker feed bus to the distribution alarm strip.

2

Verify an FAJ – Fuse Alarm Major is reported by the controller.

3

Remove the wire. Verify the alarm clears.

Repeat test for each distribution panel or sub-system.

ac Fail Alarms

25

Step

Action

1

Turn off AC circuit breaker feeding a single rectifier.

26

2

Verify ACF – AC Fail Minor is reported for the correct rectifier ID.

3

Restore input and verify alarms clear and the controller returns to Normal.

4

Remove input from two or more rectifiers.

5

Verify MACF – Multiple AC Fail Major is reported for the correct rectifier IDs.

6

Turn on input circuit breaker turned off in Step 1 and verify alarms clear and the controller returns to Normal.

Battery On Discharge Alarms

27

Step

Action

1

Change BD alarm to 2 volts below float voltage (Menu > Configuration > Float Settings > Voltage Alarms >

BD).

2

Adjust the load to 50 amperes.

3

Verify the BD alarm occurs when the system voltage decreases to BD threshold.

4

Verify the BD alarm clears once the voltage has exceeded 0.5V above the BD alarm threshold.

5

Restore the BD alarm threshold to its previous setting.

High Voltage Alarms

Step

Action

1

Confirm the HV alarm threshold (Menu > Configuration > Float Settings > Voltage Alarms > High Minor).

2

Adjust the float voltage to a value greater than this threshold

(Menu > Configuration > Float Settings > Set Point).

3

Verify an HV alarm is reported by the controller.

4

Restore the float voltage back to its original setting.

5

Restore the HV setting back to its original setting.

6

Verify the alarms clear and the controller returns to Normal.

25

Rectifier Input Fail Controller Alarms: is displayed and labeled “ACF” and “MACF”.

Input Fail Rectifier LED: non-Eco rectifiers LED is labeled “ACF”. Eco rectifiers LED is labeled “INF” (INput Fail).

26

DC fed Eco rectifiers do not report a failure (INF) when DC input is removed.

27

Eco systems do not alarm for battery discharges and may have BD thresholds settings different than non-Eco

systems.