Table 6 alarm signals - pulsar plus – GE Industrial Solutions H5692448 Power Systems Infinity M1 (NE-M) User Manual

Page 45

Advertising
background image

NE-M

Installation Guide

H5692448

CC848815325 r06 May 2013

45

Step

Action – Pulsar Plus

4

Output Alarm Connector

Connect and wire remote alarm output circuits to Connector J4. J4 is output alarm connector.

Utilize cable as necessary to obtain the desired connections to the outputs shown below.

Output Alarm Cable comcodes for J4 are: 50ft: CC848817635, 150ft: CC848817643.

Table 6 Alarm Signals - Pulsar Plus

Pin #

Wire Color

Signal

Name

18

Pin #

Wire Color

Signal

Name

18

Defaults

Standard

Eco

1

(BL)

PCR

11

(BL-BK)

PCR_C

PCR

(Power Critical)

2

(O)

PMJ

12

(O-BK)

PMJ_C

PMJ

(Power Major)

3

(G)

PMN

13

(G-BK)

PMN_C

PMN

(Power Minor)

4

(W)

UR1

14

(W-BK)

UR1_C

BD

(Battery on

Discharge)

5

(BK)

UR2

15

(BK-W)

UR2_C

VLV

(Very Low Voltage)

6

(BL-W)

UR3

16

(BL-R)

UR3_C

FAJ

(External Fuse Major)

7

(O-R)

UR4

17

(R)

UR4_C

ACF

(rectifier input AC or

DC) Fail)

Generator

Start/Stop

8

(G-W)

UR5

18

(R-G)

UR5_C

RFA

(Rectifier Fail)

9

(W-R)

UR6

19

(R-W)

UR6_C

MRFA

(Multi Rectifier Fail)

10

(BK-R)

UR7

20

(R-BK)

UR7_C

HV

(High Voltage)

Generator

Maintenance

5

Network (LAN) Connection (Optional)

Connect to network.

The controller provides an Ethernet connection for a LAN and or Craft port connection. Connector J5 provides

a standard RJ45 shielded receptacle connection for a standard Cat-5 connection to the controller’s

10/100Base-T port. This port has two main modes of operation: Server mode, LAN mode (Static and DCHP

Client). In server mode the port can be used as a local Craft interface. In this mode, a local laptop can be

connected through J5 and its standard web browser used to directly access the controller by typing in

network address

http://192.168.2.1

. A connection should never be made between the controller and LAN

while the controller is in Server mode.

Is the controller equipped with the Modem Option?

Yes – go to Step 6.

No – go to Step 7.

18

Relays are reconfigured for specific use for specific Eco applications.

Advertising