Connect batteries, Tray mounted batteries, Battery disconnect switch connection – GE Industrial Solutions H5692448 Power Systems Infinity M1 (NE-M) User Manual

Page 29: Figure 37 battery disconnect switch, Figure 38 batt disconnect switch input bus, Figure 39 battery cable -48v

Advertising
background image

NE-M

Installation Guide

H5692448

CC848815325 r06 May 2013

29

Connect Batteries

Tray Mounted Batteries

Go to the procedure for the disconnect method provided on the trays:

Battery Disconnect Switch Connection
Anderson Connector Connection
Direct to Battery Bus Connection

Battery cables from factory mounted battery trays are factory installed and terminated to the distribution panel.

Battery Disconnect Switch Connection

Step

Action

1

Ensure disconnect switch is in the OFF position

(downward) prior to making any connections.

Remove the two 6/32 screws to remove the

plastic cover.

Figure 37 Battery Disconnect Switch

2

Connect one end of the 2/0 cable to the input bus

of the disconnect switch with 1/4-20 hex nuts

provided.

Torque to 65 in-lb – 7/16” socket.

Figure 38 Batt Disconnect Switch Input Bus

3

Re-attach clear plastic cover to disconnect

switch and secure with 6-32 screws.

4

Connect Battery Cable (hot side)

48V Battery Strings


Connect the 2/0 cable between the V- post of the

left-most battery and the input bus of the

disconnect switch.

Torque to battery manufacturer’s specification.

Figure 39 Battery Cable -48V

Disconnect

Switch

Input Bus

Advertising