Table 1 Rectifiers and Converters

Rectifier/Converter

Input

Output

Eco Compatible

Eco Rectifier

blue

NE050ECO48ATEZ

ac 110/208/220/240 Vac
dc 60Vdc (+/-30V)

to 310Vdc (+/-150)

11A max

48V, 50A

Yes

7

Eco Rectifier

orange

NE100ECO24TEZ

ac 110/208/220/240 Vac
dc 60Vdc (+/-30V)

to 310Vdc (+/-150)

11A max

24V, 100A

8

Yes

7

Converter

blue

NE040DC48ATEZ

24 Vdc

48V, 40A

Yes

NE030DC48A

48V, 30A

Yes

Converter

orange

NE075DC24A

48 Vdc

24V, 75A

Yes

Rectifier

blue

NE075AC48ATEZ

110/208/220/240 Vac

48V, 75A

9

AC Only

10

NE050AC48ATEZ

110/208/220/240 Vac

48V, 50A

NE050AC48A

11

208/220/240 Vac

Rectifier

orange

NE100AC24ATEZ

110/208/220/240 Vac

24V, 100A

AC Only

10

NE100AC24A

11

208/220/240 Vac

NE850 Slot Filler

7

REQUIRED – Eco rectifiers in all DC (PV or solar) powered rectifier positions.

RECOMMENDED – Eco rectifiers in all Eco system rectifier positions.

NOT RECOMMENDED – non-Eco rectifiers in Eco systems.

Non Eco rectifiers will not function properly when powered by DC (PV or solar) input in Eco systems.

Use of non-Eco rectifiers in Eco systems increases the risk of improperly filling all system rectifier positions.

Non Eco rectifiers may be installed in AC powered rectifier positions of Eco systems.

8

44A with 120Vac input

9

22A with 120Vac input

10

NOT RECOMMENDED for use in Eco systems - Non Eco rectifiers will not function properly when powered by DC

(PV or solar) input in Eco systems.

Use of non-Eco rectifiers in Eco systems increases the risk of improperly filling system rectifier positions.

11

Non-TEZ rectifiers are no longer orderable and have lower efficiency than TEZ rectifiers