Specifications and Application

• Specifications and ordering information are in the Infinity M Product Line Brochure available at

www.gecriticalpower.com

• External Surge Protective Device (SPD) is required on all AC inputs.
• Equipment and subassembly ports: 1. are suitable for connection to intra-building or unexposed wiring or cabling;

2. can be connected to shielded intra-building cabling grounded at both ends.

• Grounding / Bonding Network – Connect to an Isolated Ground Plane (Isolated Bonding Network) or an Integrated

Ground Plane (Mesh-Bonding Network or Common Bonding Network).

• Installation Environment - Install in Network Telecommunication Facilities, OSP, or where NEC applies.
• Battery return may be either Isolated DC return (DC-I) or Common DC return (DC-C).