14.3.3 On-/Off-Ratio Control (COND_CONTROL_RATIO)

This module allows a simple On-/Off ratio control of the conductivity with an optional interface to the
"Biocide-Dosing" module.

These modules
are explained
below.

Figure 42: COND_CONTROL_RATIO

Ratio

Since the quality of the incoming water (make-up water) is varying, the conductivity of the incoming
water is measured and used for determining the current set point of the conductivity control of the
system water.

The internal calculation of the set point SP takes place as described below:

PV2

*

k

x

ratio

PV2

SP

SP = kx * PV2

SP-Limitation, so that SP
is within alarm limits
(Alarm-, Alarm+) of PV1

SP > SPLim
(SP has to be
greater than offset)

Alarm-

Alarm-

Alarm+

Alarm+

Output

In-

put

SP

Lim

SPLim

Output

In-

put

Figure 43: Set point calculation (COND_CONTROL_RATIO)

First the process value is multiplied with the ratio factor Kx. Afterwards the result is limited to the
input alarm limits

of the System Channel conductivity input, in order to avoid providing a set point,

which causes later on an input alarm. Then the result is checked, whether it is smaller than the
required set point minimum SPLim ("Set Point minimum", internal value). If not, it will be set to SPLim.

The set point minimum SPLim is calculated internally in the following way:

SPLim

= PV2

(of Make-Up Channel)

+ Offset + Switching Hysteresis

[µS/cm]

If a sensor/input error occurs on Make-Up-Channel, the last valid calculated set point will be
used!