14.3.2 PI-Control

(COND_PI)

This module permits a Proportional Integral (PI)-Control of the conductivity with an optional interface to
the "Biocide-Dosing" module. The functionality is same as in the conductivity On/Off-Controller
COND_CONTROL, except the internal PI-Controller.

These modules
are explained
below.

Figure 39:
COND_PI

Pre-bleeding and "Biocide Dosing" Module

It is the same module as described in the chapter above, (Chapter 14.3.1 in the section "Pre-bleeding
and "Biocide Dosing" Module".

PI Controller

The description of the Proportional Integral (PI)-Controller is consistent to the PI-part of the PID
Controller in section “PID Controller” in chapter 14.2. Specifics / differences are described below.

Proportional part / Module sense of action:

The normal module sense of action is defined:

Proportional

part:

Yp[%]

)

(

PV

SP

Kp

=

It can be illustrated as shown in the following figure:

Lim+

Lim-

PV

Proportional
Controller Output

SP

Module - sense of action: normal

Lim+

Lim-

PV

SP

Module - sense of action: inverted

Proportional
Controller Output


Figure 40:
Sense of action of the
modules
(COND_PI
and
COND_PI_RATIO)

Deadband:
A deadband doesn’t exist for this module.