Maximum output timer (mot), Total dissolved solids (tds)-display, Processdata and data logging – Burkert Type 8620 User Manual

Page 107: Parameter (codelevel: operator)

Advertising
background image

mxCONTROL Type 8620


Page 107

Maximum Output Timer (MOT)

Compare the description of the Maximum Output Timer in section "Maximum Output Timer (MOT)" in
chapter 14.3.2.

Total Dissolved Solids (TDS)-Display

The TDS display is only available for the conductivity process value of the System Channel.

Please refer to the description on section "Total Dissolved Solids (TDS)-Display" in chapter 14.3.1

Processdata and Data Logging

Display-Presentation

Displayed data

Abbre-
viation
(menu)

Full

Screen

Trend

chart

Line

Data-

Log.

Notes

Process value System Channel

PV1

x x x

x

Process value System Channel
(in ppm)

PV1

x x

x

Only if TDS-Display
is configured

Process value Make-Up
Channel

PV2

x x x

x

Set point

SP

x x

x

Set point vs. Process value
System Channel

SP/PV1

x

Module output

CMD

x x

x

Alarm Maximum Output Timer

x

x

is displayed only if
MOT was enabled
and is expired;
Data log in controller
output

Parameter (CodeLevel: Operator)

Parameter

Abbreviation
(menu)

Value range

Default values

(after successful download of Cfg-
File)

Sample Time

Tsample

0.05/0.1 … 60.0 s

0.2 s

For Make-Up Channel:
Ratio

Kx

1.2 … 9.9

2.0

Offset

Offset

0 … 999.9 µS/cm

10 µS/cm

For System Channel:
Gain/amplification factor

Kp

0.001 … 9999.0
(in % / unit)

10.0

Reset time

Tn

0.1 ... 9999.0 s

9999.0 s

Lower output limit

Lim-

0.0 % ... Lim+

0.0 %

Upper output limit

Lim+

Lim- ... 100.00 %

100.00 %

Safety output value

CMDsafe

0.0 ... 100.00 %

0.0 %

Maximum output timer (MOT)
Maximum output time (*)

+Tm

1 ... 10800 s

10800 s

For TDS-Calibration:
Conductivity value (**)

PV cal

1 ... 99999 (in units of the
assigned process value
input)

1000

TDS value (**)

TDS cal

1 ... 99999 ppm

800 ppm

(*) will be only displayed if the parameter “MOT” is configured as “Yes” in the menu „Configuration“
(**) will be only displayed if the parameter “TDS Disp” is configured as “Yes” in the menu „Configuration“