Configuration (codelevel: specialist) – Burkert Type 8620 User Manual

Page 68

Advertising
background image

mxCONTROL Type 8620


Page 68

Configuration (CodeLevel: Specialist)

Configuration

Access
via
Cfg.-
menu

Access
via XML-
Cfg.-File

Abbre-
viation
(menu)

Value range

Default values

(after factory reset or at
start of Cfg-File-Download)

Enabling / disabling
input

rw rw Input On/Off

Off

Special input function

rw

rw

SpecFunc 0: none

1: Square root of PV

0

Process value
scaling: unit

rw rw Scal

Unit

Units of Chem.
Analysis, Volume,
Flow, Temperature,
Misc.

No Unit

Process value
scaling: Low scaling
value @ 4 mA

rw

rw

Scal-

-99999 … Scal+

-99999

Process value
scaling: High scaling
value @ 20 mA

rw

rw

Scal+

Scal- … 99999

99999

Process value
scaling: Sense of
action

rw

rw

ScalDir

Rise / Fall

Rise

Filter stage

rw

rw

Filter

0 ... 9

0

Process value alarm
Alarm mode

rw

rw

Mode

Off, Alarm,
Alarm & Warn

Alarm & Warn

Low alarm limit (*)

rw

rw

Alarm-

-99999 … Alarm+

-99999

High alarm limit (*)

rw

rw

Alarm+

Alarm- … 99999

99999

Alarm hysteresis (*)

rw

rw

AlarmHys

0.1 … 10.0 % of
range (Scal- …
Scal+)

1.0 %

Low warning limit (*)

rw

rw

Warn-

Alarm- … Warn+

-99999

High warning limit (*)

rw

rw

Warn+

Warn- … Alarm+

99999

Warning hysteresis (*) rw

rw

WarnHys

0.1 … 10.0 % of
range (Scal-…Scal+)

1.0 %

Calibration
Calibration funtionality rw rw CalibFct

No/Yes

No

Offset (@4mA) (**)

rw

rw

Offset

-99999 … +99999
in [Scal Unit] at 4 mA

0.0

Slope (**)

rw

rw

Slope

if ScalDir = Rise:
0 … +99999
if ScalDir = Fall:
-99999 … 0
in [Scal Unit] / [mA]

16 mA / [Scal+ - Scal-]

Apply Default values
to Offset and Slope
(**)

-- w Default

values

(*) will be only displayed if the corresponding Alarm Mode is selected
(**) only visible if CalibFct = Yes