mxCONTROL Type 8620


Page 147

Warning or
Error message

Displayed as

Displaying
interval

Cause

Remedy

XX = 01 … 08, 21, Y = 1:

The cause is often a power-
on-reset or software reset
while updating Eeprom
values.

Report this error to Bürkert
Sales Center.

All other errors:

Proceed as for XX = 00,
Y = 1. If this error occurred
more than once, then the
device has to be replaced.

Contact the Bürkert Sales
Center regarding replacing
the device.

Email failed

short message

Error while communicating
with SMTP server -
transmission of email failed.

Refer to error message
“SMTP Error X Y”, which
was displayed before.

Error ISR
Timing X

permanent
message

once

Internal Timing Error in
cyclical executed function.

Contact your local Bürkert
Sales Center and provide
the current configuration
and parameter files.

Factory Reset

short message

once

All configuration and
parameter data is reset to
default values and the
mxCONTROL can initially no
longer work as controller.

The continuation of the
operating as controller is
possible after the downloa-
ding of a new configuration
and parameterization.

False code

short message

once

Wrong code for current
required code level.
Access to target menu item(s)
is denied.

Input the right code for the
required code level.

Fault Ethernet

permanent
message

Once each
minute - as
long as fault
is not
remedied or
Ethernet
function is
disabled

Communication with internal
Ethernet module failed.

Contact the Bürkert Sales
Center if the error occurs
more often.

Fault RTC

short message

permanent
message

once

once

Communication with internal
RTC failed. Time is generated
internally.

Initialization of RTC failed or
RTC delivered inconsistent
time.

Contact the Bürkert Sales
Center if the error occurs
more often.

Set the clock. Then restart
the device. If the error
occurs again (more than 3
times), contact the Bürkert
Sales Center.

Input Fault

(Input state: FI)

Icon in menu
Processdata/
Inputs

Icon/flashing
message in full
screen view of
correspondent
Process Value

as long as
fault is not
remedied

Analog input:

4…20 mA: Current below
approx. 3.5 mA

Pt100:
Resistance < input range or
Pt100 not connected

Check the wiring from the
corresponding sensor to
mxCONTROL.