Low pass filter, Process value) alarm, Configuration (codelevel: specialist) – Burkert Type 8620 User Manual

Page 71

Advertising
background image

mxCONTROL Type 8620


Page 71

Low Pass Filter

Please refer to the description of the low pass filter in section 12.2.1.

(Process Value) Alarm

Please refer to the description on the process value alarm in section 12.2.1.

Configuration (CodeLevel: Specialist)

Configuration

Access
via Cfg.-
menu

Access via
XML-Cfg.-
File

Abbre-
viation
(menu)

Value range

Default values

(after factory reset or
at start of Cfg-File-
Download)

Enabling / disabling
input

rw rw Input On/Off

Off

Process value
scaling: unit

rw

rw

Scal Unit

°C, °F, °Rank, K

°C

Process value
scaling:
low scaling value

rw rw Scal- -200 ... Scal+ (in selected

unit)

-200

Process value
scaling:
high scaling value

rw rw Scal+

Scal- ... 800 (in selected
unit)

+800

Correction Value

rw

rw

CorVal

Depending on the selected
unit:
-20.0 ... + 20.0 °C or K -
36.0 ... + 36.0 °F or °R

0.0 °C

Filter stage

rw

rw

Filter

0 ... 9

0

Process value alarm
Alarm mode

rw

rw

Mode

Off, Alarm,
Alarm & Warn

Alarm & Warn

Low alarm limit (*)

rw

rw

Alarm-

-99999 … Alarm+

-99999

High alarm limit (*)

rw

rw

Alarm+

Alarm- … 99999

99999

Alarm hysteresis (*)

rw

rw

AlarmHys

0.1 … 10.0 % of range
(Scal- … Scal+)

1.0 %

Low warning limit (*)

rw

rw

Warn-

Alarm- … Warn+

-99999

High warning limit (*) rw

rw

Warn+

Warn- … Alarm+

99999

Warning hysteresis (*) rw

rw

WarnHys

0.1 … 10.0 % of range
(Scal- … Scal+)

1.0 %

(*) will be only displayed if the corresponding Alarm Mode is selected