Mxcontrol type 8620 – Burkert Type 8620 User Manual

Page 177

Advertising
background image

mxCONTROL Type 8620


Page 177

Legend

State PV (English)

State CMD (English)

Line 1:

(User defined) names of Control Functions

AH

Higher Alarm

Au

Automatic Mode - the output is calculated by assigned controller

Line 2:

Configured modules (short module name)

AL

Lower Alarm

CM

Calibration mode: 4-20mA output is currently calibrated

Line 3:

Internal code for PC-Tool

CM

Calibration mode: 4-20mA

Fc

Calibration Data Fault (only 4…20 mA Outputs)

Line 4:

Data format

input is currently calibrated fF

Output value set to "0" - Cause: The flow switch is active and causes an alarm: No flow

Line 5:

Internal names of the monitored variables

without Hold function

fo

Output value is forced/controlled by another module

Line 6:

User defined name of assigned input/output

FA

Internal AD-Fault

fS

Output value set to "0" - Cause: The binary system switch is active

Line 7:

Units of observed variables

Fc

Calibration DataFault

Ma

Manual Mode - the output has to be controlled by the operator

Biocide Dosing "State Ch1" and "State Ch2"

FC

Configuration Fault

OF

Output Fault (4…20mA-Outputs)

0 Manual

Mode

FI

Input Fault

YA

Output of pH controller set to "0" - Cause: Alarm: ASL Pumps Stop - The corrosion rate

1

Ready - Waiting for next dosing start

FS

Sensor Fault

has exceeded the ASL limit

2

Prebleed

HO

Value Hold during

YF

Output value set to "0" - Cause: "Out Fails" (Maximum Output Timer(MOT)) has expired

3

Main Dose

User Calibration

YS

Output is set to the value of "YSavePos" - Cause: Input or sensor error

4

Delay after Main-Dose

nA

Input not active

on at least one assigned module input

5

Post Dose

OK

Value

OK

6

Delay after Post-Dose

WH

Higher

Warning

7

Stand-By (System switch active, Biocide Dosing not active)

WL

Lower

Warning

8

No Flow (Flow switch active, Biocide Dosing not active)

Other values are undefined