Output override, Processdata and data logging, Parameter (codelevel: operator) – Burkert Type 8620 User Manual

Page 121

Advertising
background image

mxCONTROL Type 8620


Page 121

Output Override

The output of this module is influenced at certain states (see figure).

Automatic

Manual

Operation
mode

Manual
Output
Value

0

1

Sensor-/Input
fault

Safety
Output
Value

Module

Output CMD

0

1

System
Switch

0 %

0

1

Flow
Switch

0 %

Output from

Output Limiter

System Switch
override function
can be enabled
or disabled

Flow Switch
override function
can be enabled
or disabled

Sensor-/Input
fault of assigned
Temperature or
Flow-Input

Figure 59: Output override (O2_SCAV_CTRL_RATIO).

Processdata and Data Logging

Display-Presentation

Displayed data

Abbre-
viation
(menu)

Full

Screen

Trend

chart

Line

Data-

Log.

Notes

Flow Process value

PV1

x x x

x

Temperature Process Value

PV2

x x x

x

(calculated) Oxygen

O2

x x

x

Module output

CMD

x x

x

Parameter (CodeLevel: Operator)

Parameter

Abbrevia-
tion
(menu)

Value range

Default values

(after successful download of
Cfg-File)

Lower output limit

Lim-

0.0 … Lim+

0.0 %

Upper output limit

Lim+

Lim- … 100.0 %

100.0 %

Safety output value

CMDsafe

0.0 … 100.0 %

0.0 %

Oxygen Alarm

(Range: 0 … 100 % Sat *) or 0.1 .. 14.55mg/L)

Low alarm limit

Alarm-

0.0 % Sat… Alarm+ or
0.1 mg/L … Alarm+

0.0 %Sat or
0.1 mg/L

High alarm limit

Alarm+

Alarm- … 100 % Sat or
Alarm- … 14.55 mg/L

100.0 %Sat or
14.55 mg/L

Alarm hysteresis

AlarmHys

0.1 … 10.0 % of oxygen range

1.0 %

Low warning limit

Warn-

Alarm- … Warn+

0.0 %Sat or 0.1 mg/L

High warning limit

Warn+

Warn- … Alarm+

100.0 %Sat or 14.55 mg/L

Warning hysteresis

WarnHys

0.1 … 10.0 % of oxygen range

1.0 %

*) Sat means Saturation