Output override, Maximum output timer (mot) – Burkert Type 8620 User Manual

Page 126

Advertising
background image

mxCONTROL Type 8620


Page 126

Output Override

The output of this module is influenced at certain states (see figure).

Automatic

Manual

Operation
mode

Manual
Output
Value

0

1

Sensor-/Input
fault

Safety
Output
Value

Module
Output

CMD

0

1

System
Switch

0 %

0

1

Flow
Switch

0 %

Output from
PI-Controller

System Switch
override function
can be enabled
or disabled

Flow Switch
override function
can be enabled
or disabled

0

1

0 %

Maximum
Output
Timer is
expired

Optional,
if configured

Figure 65: Output override (CL_ORP)

Maximum Output Timer (MOT)

This function monitors controller output of the chlorine/redox controller in automatic Mode. If the
controller output emits the maximum control output longer than the defined maximum control output
time (+Tm), then the controller output will be overridden with "0 %".

In this case an alarm “Out fails” is generated and the common alarm relay is actuated, too.

The internal timer counting the period of the maximum control output will be reset if the control output
is smaller than the maximum control output and the alarm has not yet been triggered. The maximum
output is determined by the parameter "Upper output limit Lim+".

The Maximum Output Timercan be enabled/disabled through the configuration. For a general
description of the MOT refer to chapter 14.1.5.

The chlorine/redox controller output will be overridden with 0 % until the operator
acknowledges the alarm message with the soft key buttons in the process data menu,
even if operation mode was changed.