3 (remote) device access via pc-tool – Burkert Type 8620 User Manual

Page 52

Advertising
background image

mxCONTROL Type 8620


Page 52

Configuration

Access
via Cfg.-
menu

Access
via XML-
Cfg.-File

Abbrevia-
tion
(menu)

Value range

Default values

(after factory reset or
at start of Cfg-File-
Download)

Notification
Notification via email

rw

rw

Via email

Yes, No

No

SMTP mail server (#) (***)
IP address of mail server

rw

rw

IP

0.0.0.0 …
255.255.255.255

0.0.0.0

Port number for SMTP

rw

rw

Port

0 … 65535

25

Email (***)
Device´s sender address
(#)

rw rw From

(sender)

max. 47 characters
(***** *)
[[email protected]]

Recipient 1

rw

rw

To (reci-
pient 1)

max. 39 characters
[[email protected]]

Recipient 2

rw

rw

To (reci-
pient 2)

max. 39 characters
[[email protected]]

Email 1, Email 2, Email 3 (***)
Email Trigger

rw

rw

Trigger

On, Off

On

Email priority (for display in
email program on PC)

rw

rw

Priority

1 (highest) …
5 (lowest)

1

Renotification interval (****) rw

rw

ReNotify

0 (off) … 10800 min

0 min

Email subject

rw

rw

Subject

max. 23 characters
[a-zA-Z0-9 _.:/!+*-]

Email
1: Alarm
2: Warning/Error
3: Device Restarted

(#)

Ask your local network administrator for the right settings.

(*)

Only visible, if Static IP = Yes

(**)

Only visible, if Static IP = No

(***)

Only visible, if Via email = Yes

(****)

Only available for email 1 and email 2

(*****) ID = Device ident no. (8 digits with ledig zeros),

SERIAL = Device serial no. (7 digits with ledig zeros)

(***** *) Empty string activates default sender address: 8620_ID_SERIAL with (*****)

11.5.3 (Remote) Device access via PC-Tool

Remote device access allows operating the controller via Ethernet (devices with Ethernet option only)
or via USB.

Remote device access can be disabled only directly at the device – in the configuration menu:

USB:

Configuration \ Communication \ USB \ PCToolAccess

On (default) / Off

Ethernet:

Configuration \ Communication \ Ethernet \ PCToolAccess

On (default) / Off

Configuration of PCToolAccess is not stored in the configuration file.

The PCToolAccess has to be disabled manually again in case of factory reset.

The device can handle only one remote device access at one time.