mxCONTROL Type 8620


Page 127

Processdata and Data Logging

Display-Presentation

Displayed data

Abbre-
viation
(menu)

Full

Screen

Trend

chart

Line

Data-

Log.

Notes

Process value

PV

x x x

x

Set point

SP

x x

x

Set point vs. Process value

SP/PV

x

Module output

CMD

x x

x

Alarm Maximum Output Timer

x

x

displayed only, if
MOT enabled and
expired;
Data log in Module
output

Parameter (Code Level: Operator)

Parameter

Abbrevia-
tion
(menu)

Value range

Default values

(after successful download of
Cfg-File)

Sample Time

Tsample

0.05/0.1 … 60.0 s

0.2 s

Set point

SP

Scal- …Scal+ of the assigned input

Scal- + ((Scal+ - Scal-) /2)

Gain/amplification factor

Kp

0.001 … 9999.0 (in % / unit)

10.0

Reset time

Tn

0.1 … 9999.0 s

9999.0 s

Lower output limit

Lim-

0.0 … Lim+

0.0 %

Upper output limit

Lim+

Lim- … 100.0 %

100.0 %

Safety output value

CMDsafe

0.0 … 100.0 %

0.0%

Maximum output timer (MOT)
Maximum output time (*)

+Tm

1 ... 10800 s

10800 s

(*) will be only displayed if the parameter “MOT” is configured as “Yes” in the menu „Configuration“

Configuration (Code Level: Specialist)

Configuration

Access
via
Cfg.-
menu

Access
via XML-
Cfg.-File

Abbreviation
(menu)

Value range

Default values

(after factory reset or
at start of Cfg-File-
Download)

Module active/not active rw

rw

Module

On/Off

Off

Inversion module sense
of action

rw

rw

InvMod

Yes / No

No

System switch override

rw

rw

SSOR

Yes / No

No

Flow switch override

rw

rw

FSOR

Yes / No

No

Maximum Output Timer

rw

rw

MOT

Yes / No

No