mxCONTROL Type 8620


Page 136

Figure 71: Parameterizing the Biocide 14-Day Dosing Timer

Configuration (CodeLevel: Specialist)

Configuration

Access
via Cfg.-
menu

Access
via XML-
Cfg.-File

Abbrevia-
tion
(menu)

Value range

Default values

(after factory reset or
at start of Cfg-File-
Download)

Module active/not active rw

rw

Module On/Off

Off

Channel mode

r

rw

ChMode

Dual, Single

Dual

Reference-Date for Week1

rw

rw

Ref.Date
Week 1

yyyy-mm-dd (Menu)

2007-01-01 (Menu)

Max. pre-bleed timer for
active channels

rw

rw

MTPB

Yes / No

No

Type of link to conductivity
module

-- rw -- NONE, NORMAL,

RATIO

NONE

Link to conductivity module
(pre-bleed)

r rw Link

linked

function

-- (Menu)
0 (File)

System switch override

rw

rw

SSOR

Yes / No

No

Flow switch override

rw

rw

FSOR

Yes / No

No

The "Dosing Events” must be selected as "On" in order to actually activate the dosing
events Dos 1 to Dos 8 for this day.

Even if

all dosing events of a day are marked as “Off”, their start time and the „bells“ will

be displayed!

For prevention of the expiring of dosing events in a channel in automatic mode, the start
times in a channel should be chosen due to the following rule:

Start Time >=

Start time previous dos. + dosing time previous Dos(Tdose) + 1min

+ Channel delay after main dos. (Tm1) + Channel delay after post-dos. (Tm2)

+ typical duration or max. duration (+TmPB) for pre-bleed phase

(Start time previous dos.: Start time of the chronologically previous dosing event)