Channel output in manual mode – Burkert Type 8620 User Manual

Page 133

Advertising
background image

mxCONTROL Type 8620


Page 133

The Figure 69 demonstrates the relationship between system water conductivity and biocide dosing.

Delay Tm1

Bleed lock-out Tm2

(Tm2 adjustable)

Time

Conductivity

Bleed

Biocide Dosing

Biocide Dosing Off

Biocide Dosing On

Bleed Valve open

Bleed Valve closed

Control limits of
Conductivity

Pre-bleed limit of
conductivity before
biocide dosing

(Main dosing

time: 2/3Tdose)

Time

Time

Biocide timer

starts pre-bleed

(time scheduled)

(Post dosing

Time: 1/3Tdose)

Dosing time Tdose

Figure 69: Strategy of biocide dosing

Rules for the biocide dosing:

● A

new biocide dosing event

will be only triggered, if the previous biocide dosing process on

this channel is finished. The new biocide dosing event in between expires.

● Both

biocide dosing

channels work independently.

● If a biocide dosing process is running on one channel and the second channel begins, too, the

internal status of the conductivity controller

will not be changed:

● If the channel one has left the pre-bleed, the pre-bleed for the later starting second channel

will be skipped and the second channel will begin immediately with the dosing process.

● If channel one is in the pre-bleed phase and the second channel starts, too, the minimum of

the pre-bleed limits from both channels

will be taken in order to determine the end of the

pre-bleed process. The max. duration of the pre-bleed phase is determined by the greater one
of the max. pre-bleed durations of both channels.

● If both biocide dosing channels are active, the control will return to the assigned

conductivity controller

if both channels have finished the dosing process.

● If at least one of the digital inputs is configured as a binary input for system status or as a flow

switch and if at least one of these binary inputs gets or is active, all active biocide dosing
processes will be cancelled and no new biocide dosing events will be triggered and started.

Channel Output in Manual Mode

In manual Mode all active biocide dosing processes are cancelled. The control of biocide dosing is
assumed by the operator, who must now manually control the biocide dosing by operating the dosing
valves with soft keys on the „Type 8620 mxCONTROL“ (in the "Process Data" menu).