15 Alarm and Error Messages

15.1 Alarm

function

This function actuates the common alarm output whenever a controlled variable exceeds adjustable
upper and lower alarm limits or the datalogging failed.

If an alarm occurs in at least one of the processes (see Figure 10), this is indicated by the yellow
flashing LED on the A/M-Key

.

Note!

If a switching hysteresis is present, the triggering of the alarm is impacted by the value

definition (e.g.: Switching takes place above and below the alarm set point to prevent excessive
switching frequency - compare Figure 75).

Warning limits

can be additionally set for displaying and logging purposes only.

Figure 75:
Alarm/warning -
switching hysteresis

Adjustable alarm parameters:

Analog inputs

Digital inputs

Oxygen

4-20mA, Pt100

Frequency

Binary

Module O2_SCAV

_CTRL_RATIO

High alarm limit Alarm+

X X -

X

Low alarm limit Alarm-

X X -

X

Switching alarm hysteresis AHyst

X X -

X

Low or High Alarm with delay

- -

X -

For displaying and logging purposes only:
High warning limit Warn+

X X -

X

Low warning limit Warn-

X X -

X

Switching warning hysteresis WarnHys

X X -

X