6 technical data, 1 technical specifications – Burkert Type 8620 User Manual

Page 17

Advertising
background image

mxCONTROL Type 8620


Page 17

6 Technical

Data

6.1 Technical

Specifications

These operating instructions are valid from

Firmware revision:

C.00.00.00

General Details of the Device

Enclosure

with sealed keypad and display

Enclosure outer dimensions L x W x H

230 x 204 x 119 mm (without cable glands)

Enclosure material

PC (UL94) with transparent door and key

Weight

1.8 kg

Degree of protection

IP 65 and NEMA/UL 50, Type No. 4X, with door closed and
properly sealed cable glands,
additional cover of USB port and SD card slot

Graphic display, large and backlighted

128 x 64 dots, two colored (blue and white)

Keypads for manual operation

5 keys for user inputs

Operating temperature

0 … +50 °C

Storage temperature

-20 … +60 °C

Electrical Details

Mains voltage (power supply)

100 … 240 V AC, 50/60 Hz, no adjustment necessary

Power consumption (of mxCONTROL device)

max. 35 W (incl. sensor supply at Instrumentation Supply part)

Total power consumption
(using the internal power distribution)

max. 2400 W (at 240 V AC) or max. 1100 W (at 110 V AC)
incl. connected actuators at Power Supply part

Total input current I

in

(using internal power distr.) max. 10 A

Total output current I

out

(using the internal power distribution)

<10 A (incl. device power consumption of 35 W)

Instrumentation supply for sensors / transistor
outputs

24 V DC (±5 %), max. 1.04 A (25 W),
short circuit and overload protected

Fuse for device protection
(Instrumentation)

internal: electronic fuse, recovers automatically after fault
condition is removed

Fuse for Relays outputs

Relay outputs to be fused in external installation according to
actuators

Inrush current (typ.)

Cold start: 30 A / 230 V AC

Electrical Connections

Electrical connection Power Supply

Hardware version 1:

Screw terminals, grid 5.08 mm,

for wire gauges

0.14 … 1.5/2.5 mm

2

(AWG 26…14)

Hardware version 2:

Spring type terminal, grid 5.0 mm,

for wire gauges

0.2 … 2.5/4.0 mm

2

(AWG 24…12)

Electrical connection Instrumentation Supply

Hardware version 1:

Screw terminals, grid 3.81 mm,

for wire gauges

0.14 … 1.0/1.5 mm

2

(AWG 26…16)

Hardware version 2:

Spring type terminal, grid 3.5 mm,

for wire gauges

0.2 … 1.5 mm

2

(AWG 24…16)

Hardware version 1:

9 x M16 (PG9)

5 ... 6.5 mm cable

1 x M32 (PG21)

5 mm cable (5x)

Hardware version 2:

4 x M16 (PG9)

5 ... 6.5 mm cable

2 x M16 (PG9)

6 ... 9.5 mm cable

3 x M20 (PG13)

9 ... 13.5 mm cable

1 x M32 (PG21)

5 mm cable (5x)

(cable = outer diameter of cable)
Not used cable glands have to be sealed with appropriate
sealing bolts to guarantee the Degree of protection IP65.

Cable glands and cables

Thermal stability

(cable material):

105 °C

for cables at Power Supply part

80 °C

for cables at Instrumentation Supply part

Advertising