6 data logging file – example, Mxcontrol type 8620 – Burkert Type 8620 User Manual

Page 176

Advertising
background image

mxCONTROL Type 8620


Page 176

21.6

Data Logging File – Example

#HEADER

DatalogFile

Rev

A.00

Source

DEVICE

Device

ID

188133

Serial

1001

Firmware

ID

797645

Rev

C.00.00.00

Project

Name

Project

ABCD

Cfg-File

Name

Project_ABCD.cfg

Applied

19.04.2010 14:33:19

Param-File

Name

Project_ABCD.par

Applied

21.04.2010 12:19:52

#PROCESSDATA

line 1:

CL ORP

Cond Control

Biocide Dosing

line 2:

CL

ORP

Cd

BioDos

line 3:

0-0-1 0-0-2

0-1-1 0-1-2

0-2-1 0-3-1 1-11-1 1-11-2

1-11-7

1-11-20

1-11-21

2-8-1 2-8-2

2-8-7 2-8-20 2-8-21 3-10-24 3-10-20 3-10-21 3-10-25 3-10-22 3-10-23

line 4:

date time

hex str

fl fl fl str

fl fl str fl str

fl fl str

fl fl str fl fl str

line 5:

Date Time

LogEvent

Event

Manual
Mode

Common
Alarm PV1

State
PV1 SP CMD

State
CMD PV1

State
PV1 SP

CMD

State
CMD

State
Ch1 CMD1

State
CMD1

State
Ch2 CMD2

State
CMD2

line 6:

CL ORP

CL ORP

Cond

Bleed

Bioci-
de 1

Bioci-
de 2

line 7:

YYYY-MM-DD HH:MM:SS

mV

mV

%

µS/cm

µS/cm

%

%

%

2010-04-22

13:32:13 00000014

LogEvent

0 0 458.52

OK

500.00

0.00

fS 823.45 OK

1000.0

0.00 fS 7

0.00 fS

7

0.00 fS

2010-04-22

13:32:33 00000080

Mask:

0 0 441.87

OK

500.00

0.00

fS 901.61 OK

1000.0

0.00 fS 7

0.00 fS

7

0.00 fS

2010-04-22

13:32:40 00010000

ffffffff

0 0 441.45

OK

500.00

100.00

Au 902.08 OK

1000.0

0.00 Au 1

0.00 Au

1

0.00 Au

2010-04-22

13:32:53 00000080

0

0

442.35 OK 500.00 100.00 Au

901.59 OK 1000.0

0.00 Au 1

0.00 Au 1

0.00 Au

2010-04-22

13:32:59 00010000

0

0

441.99 OK 500.00 100.00 Au

1040.3 OK 1000.0

100.00 Au 1

0.00 Au 1

0.00 Au

2010-04-22

13:33:13 00010080

0

0

513.63 OK 500.00 0.00

Au

1040.3 OK 1000.0

100.00 Au 1

0.00 Au 1

0.00 Au

2010-04-22

13:33:17 00010000

0

0

513.63 OK 500.00 0.00

Au

779.60 OK 1000.0

0.00 Au 1

0.00 Au 1

0.00 Au

2010-04-22

13:33:20 00100000

1

0

513.63 OK 500.00 20.00

Ma

933.40 OK 1000.0

0.00 Ma 0

0.00 Ma 0

0.00 Ma

2010-04-22

13:33:33 00010080

1

0

513.74 OK 500.00 20.00

Ma

932.91 OK 1000.0

100.00 Ma 0

0.00 Ma 0

0.00 Ma

2010-04-22

13:33:53 00000080

1

0

520.74 OK 500.00 20.00

Ma

931.30 OK 1000.0

100.00 Ma 0

0.00 Ma 0

0.00 Ma

2010-04-22

13:35:00 00110000

0

0

524.10 OK 500.00 0.00

Au

933.41 OK 1000.0

0.00 Au 1

0.00 Au 1

0.00 Au

2010-04-22

13:35:05 0a010000

0

1

530.19 AH 500.00 0.00

Au

1069.2 OK 1000.0

100.00 Au 1

0.00 Au 1

0.00 Au

2010-04-22

13:35:13 00000080

0

1

532.10 AH 500.00 0.00

Au

1071.6 OK 1000.0

100.00 Au 1

0.00 Au 1

0.00 Au

2010-04-22

13:35:23 0a010000

0

1

535.38 AH 500.00 0.00

Au

--

FI

1000.0

0.00 YS 1

0.00 Au 1

0.00 Au

and so on …

Only the module outputs are logged on the output side.

Exception for transistor outputs in PWM or Fast-PWM mode:
the speed limitated output value is logged.