Burkert Type 8620 User Manual

Page 19

Advertising
background image

mxCONTROL Type 8620


Page 19

Communication

SD card

SD card capacity: minimum 64 MB, maximum 2 GB,
formatted with FAT16 file system

Up-/download of configuration data
and parameters

via USB or SD card

Data-logging

on SD card

Firmware update

via USB

USB slave interface

standard USB interface for PC communication

Ethernet interface

optional: Ethernet interface for easy diagnosis including Web
Server and email option

Extension bus interface

CAN-based bus for connection of extension units
(e.g. I/O extensions)

Controller structure

Number of control loops

max. 8 active control loops

Controller outputs/Module outputs

1) On/Off
2) Pulse frequency modulated (PFM)
3) Pulse width modulated (PWM)
4) Analog

Sample period

approx. 50 ms (with 1…4 active control loops);
approx. 100 ms (with more than 4 active control loops)

User configuration

Cascade control possible; inputs, outputs and control function
designations can be changed via configuration file

Characteristics of modules

General PID control

PID process controller for fixed value, subsequent value or
cascade control

Conductivity control

On/Off or PI control - continuous dosing through PFM, PWM or
4…20 mA analog output,
automatic or manual drain

Corrosion display

No controller function, only display of measuring values;
impact on general alarm output

pH control

PI control - continuous dosing through PFM, PWM or 4…20
mA analog output

Module for dosing of oxygen scavenger media

Proportional dosing for flow and oxygen content depending on
flow with or without temperature input

Chlorine / Redox Control

PI control - continuous dosing through PFM, PWM or 4…20
mA analog output

Batch-Dosing

Allows batching of a chemical based on volume of water
added

Biocide dosing

14-day program, 8 dosing events per channel/per day; Pre-
bleed function to optimize biocide kill time

Monitor module

Display of process values

Totalizer function

Single or dual channel flow totalizer (each having two
manually resetable totalizers)

Further functionalities

Password protection, filter; selection of engineering units,
alarm; inverse function

Norms and standards

Environment standards

IEC/ DIN IEC 60068

EMC standards

EN 61000, EN 55011

Continuation next page

Advertising