3 error messages and warnings – Burkert Type 8620 User Manual

Page 145

Advertising
background image

mxCONTROL Type 8620


Page 145

15.3

Error Messages and Warnings

Most of the error messages and warnings are displayed as a short message for approx. 2 seconds on
the display. There is an internal display buffer for maximum 20 short messages. If one of the 4 soft
keys below the display is pressed while a short message is shown, the short message will disappear.

A permanent message is displayed until the operator acknowledges the message with the OK-key.
There is an internal display buffer for maximum 10 permanent messages.

If a permanent message is already displayed and a new short message has to be displayed, then the
short message will be displayed firstly and afterwards the permanent message will be displayed again
until it is acknowledged by the operator.

Warning or
Error message

Displayed as

Displaying
interval

Cause

Remedy

4-20mA Out X
failed



short message

permanent
message



once

once

Internal communication with
the 4…20 mA output X has
failed:
more than 3 times in series

more than 20 times in series

(After a successful
communication the internal
error counter is reset.)




Contact the Bürkert Sales
Center.
The device has to be
replaced.

AD Fault

(Input state: FA)

Icon in menu
Processdata/
Inputs

as long as
fault is not
remedied

A/D-Conversion failed

If this error message occurs
more than once, then
contact the Bürkert Sales
Service.

Earlier: Download the
calibration file (Master
password needed).

If this did not function, the
device has to be replaced.

Battery failed!

permanent
message



short message

flashing mes-
sage in menu 8
(Clock)

Once after
initialization

every 60
seconds,
as long as the
clock is not
set and the
internal real
time clock has
passed the
59th second

The back-up battery of the
internal real time clock (RTC)
failed.

Year of internal clock is lower
than 2007.

The back-up battery (Type
CR 2032, 3V DC) on the
reverse side of the printed
circuit board needs to be
replaced by qualified
personnel.

Set the clock to current
date and time.

CalibFault
4-20mA In

(Input state: FK)

CalibFault
Pt100 In

(Input state: FK)

permanent
message
Icon in menu
Processdata/
Inputs

Icon/flashing
message in full
screen view of
correspondent
Process Value

once after init
of config data

as long as
fault is not
remedied

Defect Calibration data for at
least one configured 4…20
mA / Pt100 Input.

The concerned inputs will be
treated as inputs with input
fault.

Contact the Bürkert Sales
Center.