Configuration (code level: specialist) – Burkert Type 8620 User Manual

Page 76

Advertising
background image

mxCONTROL Type 8620


Page 76

→ Select

„Offset“,

press key “INPUT”

(Æ the device outputs now a current of 4 mA at the 4-20mA output X)
Measure the real current through the resistor R
Input the measured current value (via keys „+“ and „<-“),

press key "OK"

→ Select

„Span“,

press key “INPUT”

(Æ the device outputs now a current of 20 mA at the 4-20mA output X)
Measure the real current through the resistor R
Input the measured current value (via keys „+“ and „<-“),

press key "OK"

→ Select

“End”;

press key “ENTER”.

Leaving this menu item the analog output will be calibrated based on the
input values (Offset, Span) and will be re-initialized.

The user calibration data are stored in Eeprom when returning to the main
menu.

If „Factory Values“ is selected, the user calibration data will be
overwritten with the factory calibration values.

If „Factory Reset“ was activated, the user calibration data of all 4-20mA-
outputs are overwritten with factory calibration values.

Configuration (Code Level: Specialist)

Configuration

Access
via Cfg.-
menu

Access
via XML-
Cfg.-File

Abbre-
viation
(menu)

Value range

Default values

(after factory reset or
at start of Cfg-File-
Download)

Enabling / disabling
output

rw rw Output

On/Off

Off

Sense of action of the
current output

rw

rw

Dir

Rise / Fall